Liebert UPStation-GXT

DB-9 female serial interface port on the Liebert UPStation GXT UPS (700–10000 VA), providing RS-232 smart signalling and remote shutdown.

The Liebert UPStation GXT is a range of on-line UPS units produced by Liebert Corporation, covering 700 VA to 10 000 VA in 120 V, 208 V, and 240 V variants. The rear-panel communications interface is a standard 9-pin D-SUB female socket that supports both RS-232 smart serial signalling (via pins 2 and 3) and simple open-collector/emitter status outputs for low-battery and utility-fail conditions. Remote shutdown can be triggered either by applying 5–12 V DC to pin 4 during battery operation, or by shorting pin 6 to pin 5 (common) in any mode. Power-management monitoring requires the Liebert SiteNet 1 shutdown kit, which includes a proprietary interface cable and software.

9 pin D-SUB female connector layout 9 pin D-SUB female connector at the UPS

Pin#Function
1Low Battery (Optocoupler Collector: +V)
2UPS TxD
3UPS RxD
4Remote ShutDown (+5..12VDC, 10 mA max); on battery operation
5Common
6Remote ShutDown (Short to pin 5); any mode operation
7Low Battery (Optocoupler Emitter: -V)
8Utility/Mains Fail (Optocoupler Emitter: -V)
9Utility/Mains Fail (Optocoupler Collector: +V)

Notes

  • The connector on the UPS rear panel is a standard DB-9 (DE-9) female socket; the mating cable plug is male.
  • Maximum voltage and current on pins 1, 7, 8, and 9 (open-collector and open-emitter outputs) shall not exceed 80 V DC and 10.0 mA. A 330 Ω resistor is shown in the reference circuit diagram.
  • Pins 1 and 7 form the Low Battery optocoupler pair (collector and emitter respectively); pins 8 and 9 form the Utility Fail optocoupler pair (emitter and collector respectively).
  • Pin 4 remote shutdown is active only during battery operation; pin 6 remote shutdown (short to pin 5) functions in all modes of operation.
  • The same pinout applies across the full GXT product family, including the 6 kVA and 10 kVA 208 V/240 V variants.

Signals

  • Pin 1 — Low Battery — open-collector output (+V side of optocoupler); max 80 V DC, 10.0 mA.
  • Pin 2 — UPS TxD — RS-232 transmit data from UPS to host computer (smart serial mode).
  • Pin 3 — UPS RxD — RS-232 receive data from host computer to UPS (smart serial mode).
  • Pin 4 — Remote Shutdown — apply 5–12 V DC (10 mA max) to initiate shutdown; active during battery operation only.
  • Pin 5 — Common — signal common/return for all circuits.
  • Pin 6 — Remote Shutdown — short to pin 5 to initiate shutdown; active in any mode of operation.
  • Pin 7 — Low Battery — open-emitter output (−V side of optocoupler); max 80 V DC, 10.0 mA.
  • Pin 8 — Utility/Mains Fail — open-emitter output (−V side of optocoupler); max 80 V DC, 10.0 mA.
  • Pin 9 — Utility/Mains Fail — open-collector output (+V side of optocoupler); max 80 V DC, 10.0 mA.